CDU Installation Guide Page 32
Cooling Distribution Unit
OPERATION (continued)
Default 40 °F [adj. 35 to 50 °F] (low temp. alarm threshold)
Default 52 °F [adj. 45 to 75 °F] (high temp. alarm threshold)
Default 2 °F [adj. 1 to 9 °F] (low/high temp. alarm reset threshold)
Default 9 PSI [adj. 3 to 15 psi] (diff. pressure alarm threshold)
Default 3 PSI [adj. 1 to 8 psi] (alarm reset threshold)
Default 60 secs [adj. 5 to 7200 secs] (time delay prior to alarm)
Default 0 °F [adj. +/-15 °F] (sensor calibration)
Default 0 °F [adj. +/-15 °F] (sensor calibration)
Default 0 °F [adj. +/-15 °F] (sensor calibration)
Default 0 °F [adj. +/-15 °F] (sensor calibration)
Default 0 % [adj. +/-10 %] (sensor calibration)
Default 0 PSI [adj. +/-15 psi] (sensor calibration)
Default 0 PSI [adj. +/-15 psi] (sensor calibration)
Default 0 PSI [adj. +/-15 psi] (sensor calibration)
Default 0 PSI [adj. +/-15 psi] (sensor calibration)
Default 15 min [adj. 1 to 120 mins] (time delay before system reverts to auto)
Default 20 min [adj. 1 to 120 mins] (event suppression on start up)
Default Alarm [adj. alarm only / shutdown] (unit flood tray sensor operation)
Default Alarm [adj. alarm only / shutdown] (under floor sensor tape operation)
Default 143 [adj. 75 to 250] (u/f sensor sensitivity)
Default 10 secs [adj. 5 to 60 secs] (u/f sensor alarm/shutdown delay)
Default N/O [adj. normally closed, normally open] (relay operation mode)
(view all currently active warnings & alarms)
(clear all active warnings & alarms)
(view last 30 logged warnings/alarms with generated date/ time)
(clear all logged warnings/alarms)
(Raw data - for factory information only)
(new style Web server with Modbus gateway)
(older style Web server / Modbus gateway **)
8-3-1-1 Attach (attach Web server)
8-3-1-2 Remove (remove Web server)
8-3-2-1 Attach (attach modbus)
8-3-2-2 Remove (remove modbus)
8-3-2-4 Address - Default 1 [adj. 1 to 247] (modbus address)
8-3-2-5 Protocol - Default rtu [adj. rtu or ASCII] (modbus protocol)
(web server / modbus gateway operational diagnostics)
** CDUA-105-1 Web server only
CDUA-105-2 Modbus gateway only
CDUA-105-3 Web server with Modbus gateway